XP POWER Industrial Partner

CFP500PS48FE - XP Power CFP500PS48FE AC/DC; 500W Power Supply Simple Type: Power...

larger image

Request Quote
For Price
Part Number:
CFP500PS48FE
Model Number:
CFP500PS48FE
Make:
XP POWER
Lead Time:
Available
Qty In Stock:
Available

XP Power CFP500PS48FE AC/DC; 500W Power Supply Simple Type: Power Supply

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • 5 Modules in 1U Rack Space
  • Internal ORing Diodes for Hot Swap Redundancy
  • International Safety Approvals
  • Measures only 10.20” x 3.39” x 1.59”
  • Mounting Height 1U Horizontal, 2U Vertical
  • Optional 19” Rack for up to 5 Modules 2500 W
  • Universal AC Input Active PFC

Specifications

    General
  • Cooling: Internal fans with front to back airflow
  • Current Share: Single wire. Within ±5% for +12 V or ±10% for 48 V
  • Earth Leakage Current: 3 mA max at 250 VAC
  • Efficiency: 85% typical for +12 V; 82% typical for +48 V
  • Hold Up Time: 16 ms for +12 V, 10 ms for +48 V
  • Initial Set Accuracy: ±0.2%
  • Input Current: 6.9 A at 90 VAC, 2.6 A max at 230 VAC
  • Input Frequency: 47-63 Hz
  • Input Protection: Internal 10 A/250 VAC fuse
  • Input Voltage: 85-264 VAC
  • Inrush Current: 20 A max per ETS 300 132 & Bellcore
  • Isolation: 3000 VAC Input to Output; 1500 VAC Input to Ground; 500 VAC Output to Ground
  • Line Regulation: 0.1% max for +48 V
  • Load Regulation: ±0.5% max for +48 V; +12 V total (line & load) regulation ±2%
  • Minimum Load: No minimum load required
  • MTBF: 300 kHrs demonstrated
  • Operating Altitude: 2250 m
  • Operating Humidity: 30-95% RH, non-condensing
  • Operating Temperature: -20 °C to +70 °C, derate linearly from 55 °C at 10 W/°C
  • Output Voltage: +12 or +48 VDC
  • Output Voltage Trim: ±10% for +12 V or ±1.5 V for +48 V
  • Over-temperature Protection: Shuts down at +110 °C internal temp with auto recovery below +95 ºC
  • Over-Voltage Protection: 116-128% Vnom, recycle input or Remote On/Off to reset
  • Overload Protection: 110-130% typical, auto recovery
  • Power Density: 9.1 W/In3
  • Power Factor: 0.99 typical
  • Remote On/Off: On - Logic High or Open; Off - Logic Low or Short
  • Ripple & Noise: 1% max pk-pk per ETS 300-132-2, measured at 20 MHz bandwidth
  • Shock: IEC68-2-27, MIL-STD-810E, Telcordia GR-63-CORE & GR-487-CORE
  • Short Circuit Protection: 54 A max for +12 V, 25 A max for +48 V
  • Signals: DC OK, Output current monitoring, Overtemp monitor, OVP monitor
  • Start Up Delay: 2 s at mains, 20 ms using Remote On/Off
  • Start Up Rise Time: 50 ms max
  • Storage Temperature: -40 °C to +85 °C
  • Switching Frequency: 100 kHz typical for PFC stage; 200 kHz typical for main converter
  • Temperature Coefficient: 0.04%/°C
  • Transient Response: +12 V: 2% max. deviation, recovery to 1% in 300 µs for a 50% load change; +48 V: 2% max. deviation, recovery to 1% in 400 µs for a 50% load change;

 

Applications

  • None Available

Aliases

  • None Available